Mo. Code Regs. tit. 19 § 30-85.022

Current through Register Vol. 49, No. 9, May 1, 2024
Section 19 CSR 30-85.022 - Fire Safety and Emergency Preparedness Standards for New and Existing Intermediate Care and Skilled Nursing Facilities

PURPOSE: This rule establishes fire-safety and emergency preparedness requirements for new and existing intermediate care and skilled nursing facilities.

PUBLISHER'S NOTE: The secretary of state has determined that the publication of the entire text of the material which is incorporated by reference as a portion of this rule would be unduly cumbersome or expensive. This material as incorporated by reference in this rule shall be maintained by the agency at its headquarters and shall be made available to the public for inspection and copying at no more than the actual cost of reproduction. This note applies only to the reference material. The entire text of the rule is printed here.

AGENCY NOTE: All rules relating to long-term care facilities licensed by the Department of Health and Senior Services are followed by a Roman Numeral notation which refers to the class (either class I, II, or III) of standard as designated in section 198.085, RSMo 2000.

(1) Definitions. For the purpose of this rule, the following definitions shall apply:
(A) Accessible spaces-shall include all rooms, halls, storage areas, basements, attics, lofts, closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes;
(B) Area of refuge-a space located in or immediately adjacent to a path of travel leading to an exit that is protected from the effects of fire, either by means of separation from other spaces in the same building or its location, permitting a delay in evacuation. An area of refuge may be temporarily used as a staging area that provides some relative safety to its occupants while potential emergencies are assessed, decisions are made, and if applicable, evacuation has begun;
(C) Major renovation-shall include the following:
1. Addition of any room(s), accessible by residents, that either exceeds fifty percent (50%) of the total square footage of the facility or exceeds four thousand five hundred (4,500) square feet;
2. Repairs, remodeling, or renovations that involve more than fifty percent (50%) of the building;
3. Repairs, remodeling, or renovations that involve more than four thousand five hundred (4,500) square feet of a smoke section; or
4. If the addition is separated by two-(2-) hour fire-resistant construction, only the addition portion shall meet the requirements for an NFPA 13, 1999 edition, sprinkler system, unless the facility is otherwise required to meet NFPA 13, 1999 edition; and
(D) Concealed spaces-shall include areas within the building that cannot be occupied or used for storage.
(2) General Requirements.
(A) All National Fire Protection Association (NFPA) codes and standards cited in this rule: NFPA 10, Standard for Portable Fire Extinguishers, 1998 edition; NFPA 13, Standard for the Installation of Sprinkler Systems, 1999 edition; NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 1998 edition; NFPA 99, Standard for Health Care Facilities, 1999 edition; NFPA 101, The Life Safety Code, 2000 edition; NFPA 72, National Fire Alarm Code, 1999 edition; NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 1998 edition; NFPA 253, Standard Method of Test of Surface Burning Characteristics of Building Materials, 2000 edition; NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 1999 edition; NFPA 211, Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances, 2000 edition; and NFPA 101A, Guideto Alternative Approaches to Life Safety, 2001 edition, are incorporated by reference in this rule and available for purchase from the National Fire Protection Agency, 1 Battery-march Park, Quincy, MA 02269-9101; www.nfpa.org; by telephone at (617) 770-3000 or 1-800-344-3555. This rule does not incorporate any subsequent amendments or additions to the materials listed above.
(B) This rule does not prohibit facilities from complying with standards set forth in newer editions of the incorporated by reference material listed in subsection (2)(A) of this rule if approved by the department.
(C) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. I/II
(D) Facilities shall not use space under stairways to store combustible materials. I/II
(E) No section of the building shall present a fire hazard. I/II
(F) All facilities shall notify the department immediately after the emergency is addressed if there is a fire in the facility or premises and shall submit a complete written fire report to the department within seven (7) days of the fire, regardless of the size of the fire or the loss involved. II/III
(G) Following the discovery of any fire, the facility shall monitor the area and/or the source of the fire for a twenty-four- (24-) hour period. This monitoring shall include, at a minimum, hourly visual checks of the area. These hourly visual checks shall be documented. I/II
(H) All electrical appliances shall be Underwriters' Laboratories (UL) or Factory Mutual (FM)-approved, shall be maintained in good repair, and no appliances or electrical equipment shall be used which emit fumes or which could in any other way present a hazard to the residents. I/II
(3) All openings that could permit the passage of fire, smoke, or both, between floors shall be fire-stopped with a suitable noncom-bustible material. II/III
(4) Hazardous areas shall be separated by construction of at least one- (1-) hour fire-resistant construction. Hazardous areas may be protected by an automatic sprinkler system in lieu of a one- (1-) hour rated fire-resistant construction. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic closing. II
(5) The storage of any unnecessary combustible materials in any part of a building in which a licensed facility is located is prohibited. No section of the building shall present a fire hazard. I/II
(6) Oxygen storage shall be in accordance with NFPA 99, 1999 edition. Facilities shall use permanent racks or fasteners to prevent accidental damage or dislocation of oxygen cylinders. Safety caps shall remain intact except where a cylinder is in actual use or where the regulator has been attached and the cylinder is ready for use. Individual oxygen cylinders in use or with an attached regulator shall be supported by cylinder collars or by stable cylinder carts. II/III
(7) Each nursing unit may maintain only one (1) emergency-use oxygen tank in a readily accessible unit area. II
(8) Fire Extinguishers.
(A) Fire extinguishers shall be provided at a minimum of one (1) per floor, so that there is no more than seventy-five feet (75') travel distance from any point on that floor to an extinguisher. I/II
(B) All new or replacement portable fire extinguishers shall be ABC-rated extinguishers, in accordance with the provisions of NFPA 10, 1998 edition. A K-rated extinguisher or its equivalent shall be used in lieu of an ABC-rated extinguisher in the kitchen cooking areas. II
(C) Fire extinguishers shall have a rating of at least-
1. Ten pounds (10 lbs.), ABC-rated or the equivalent, in or within fifteen feet (15') of hazardous areas as defined in 19 CSR 30-83.010; II and
2. Five pounds (5 lbs.), ABC-rated or the equivalent, in other areas. II
(D) All fire extinguishers shall bear the label of the UL or the FM Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III
(9) Facilities shall provide every cooking range with a range hood and approved range hood extinguishing system installed, tested, and maintained in accordance with NFPA 96, 1998 edition. The range hood and its extinguishing system shall be certified at least twice annually in accordance with NFPA 96, 1998 edition. II/III
(10) Complete Fire Alarm Systems.
(A) Facilities shall have a complete fire alarm system installed in accordance with NFPA 101, Section 18.3.4, 2000 edition. The complete fire alarm system shall automatically transmit to the fire department, dispatching agency, or central monitoring company. The complete fire alarm system shall include visual signals and audible alarms that can be heard throughout the building and a main panel that interconnects all alarm-activating devices and audible signals in accordance with NFPA 72, 1999 edition. Manual pull stations shall be installed at or near each required nurse/attendant's station and each required exit. Smoke detectors shall be interconnected to the complete fire alarm system. Specific minimum requirements relating to the interconnected smoke detectors are found in subsections (10)(I) and (10)(J) of this rule. I/II
(B) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
(C) All facilities shall have inspections and written certifications of the complete fire alarm system completed by an approved qualified service representative in accordance with NFPA 72, 1999 edition, at least annually. I/II
(D) The complete fire alarm system shall be activated by all of the following: sprinkler system flow alarm, smoke detectors, heat detectors, manual pull stations, and activation of the range hood extinguishment system. II/III
(E) Facilities shall test by activating the complete fire alarm system at least once a month. II/III
(F) Facilities shall maintain a record of the complete fire alarm system tests, inspections and certifications required by subsections (10)(B), (10)(C), and (10)(E) of this rule. III
(G) Upon discovery of a fault with the complete fire alarm system, the facility shall correct the fault. I/II
(H) When a complete fire alarm system is to be out-of-service for more than four (4) hours in a twenty-four- (24-) hour period, the facility shall immediately notify the department and the local fire authority and implement an approved fire watch in accordance with NFPA 101, 2000 edition, until the fire alarm system has returned to full service. I/II
(I) All facilities shall have smoke detectors interconnected to the complete fire alarm system in all corridors and spaces open to corridors. Smoke detectors shall be no more than thirty feet (30') apart with no point on the ceiling more than twenty-one feet (21') from a smoke detector. I/II
(J) Facilities that have a sprinkler system exemption shall have smoke detectors interconnected to the complete fire alarm system in all accessible spaces within the facility as required by NFPA 72, 1999 edition. Smoke detectors shall be no more than thirty feet (30') apart with no point on the ceiling more than twenty-one feet (21') from a smoke detector. Smoke detectors shall not be installed in areas where environmental influences may cause nuisance alarms. Such areas include, but are not limited to, kitchens, laundries, bathrooms, mechanical air handling rooms, and attic spaces. In these areas, heat detectors interconnected to the complete fire alarm system shall be installed. Bathrooms not exceeding fifty-five (55) square feet and clothes closets, linen closets, and pantries not exceeding twenty-four (24) square feet are exempt from having any detection device if the walls and ceilings are surfaced with limited-combustible or noncombustible material as defined in NFPA 101, 2000 edition. Concealed spaces of noncombustible or limited-combustible construction are not required to have detection devices. These spaces may have limited access but cannot be occupied or used for storage. I/II
(K) For each facility not having a sprinkler system exemption, each resident room or any room designated for sleeping shall be equipped with at least one (1) battery-powered smoke alarm installed, tested, and maintained in accordance with manufacturer's specifications. In addition, the facility shall be equipped with interconnected heat detectors installed, tested, and maintained in accordance with NFPA 72, 1999 edition, with detectors in all areas subject to nuisance alarms, including, but not limited to, kitchens, laundries, bathrooms, mechanical air handling rooms, and attic spaces. I/II
1. The facility shall maintain a written record of the monthly testing and battery changes. The written records shall be retained for one (1) year. I/II
2. Upon discovery of a fault with any detector or alarm, the facility shall correct the fault. I/II
(11) Sprinkler System.
(A) All facilities shall have inspections and written certifications of the sprinkler system completed by an approved qualified service representative in accordance with NFPA 25, 1998 edition. The inspections shall be in accordance with the provisions of NFPA 25, 1998 edition, with certification at least annually by a qualified service representative. I/II
(B) All facilities licensed prior to August 28, 2007, that were not required to have a complete sprinkler system in accordance with NFPA 13 shall have until December 31, 2012, to comply with NFPA 13, 1999 edition. I/II
1. Exemptions shall be granted if the facility presents evidence in writing from a certified sprinkler system representative or licensed engineer that the facility is unable to install an approved NFPA 13, 1999 edition, system due to the unavailability of the water supply. I/II
(C) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements in effect for such facilities on August 27, 2007. I/II
(D) Facilities licensed on or after August 28, 2007, or any section of a facility in which a major renovation has been completed on or after August 28, 2007, shall install and maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. I/II
(E) When a sprinkler system is to be out-of-service for more than four (4) hours in a twenty-four- (24-) hour period, the facility shall immediately notify the department and the local fire authority and implement an approved fire watch in accordance with NFPA 101, 2000 edition, until the sprinkler system has returned to full service. I/II
(12) Each floor of an existing licensed facility shall have at least two (2) unobstructed exits remote from each other. One (1) of the required exits in an existing multi-story facility must be an outside stairway or an enclosed stair that is separated by one- (1-) hour construction from each floor and has an exit leading directly outside at grade level. One (1) exit may lead to a lobby with exit facilities to the ground level outside instead of leading directly to the outside. The lobby shall have at least a one- (1-) hour fire-rated separation from the remainder of the exiting floor. I/II
(13) If facilities have outside stairways, they shall be substantially constructed to support residents during evacuation. These stairways shall be protected or cleared of ice and snow. Stairways shall be of sturdy construction using at least two-inch (2") lumber and shall be continuous to ground level. All treads and risers shall be of the same height and width throughout the entire stairway, not including landings. II/III
(14) Fire escapes added to existing buildings, whether interior or exterior, shall have at least a minimum thirty-six-inch (36") width, eight-inch (8") maximum risers, a nine-inch (9") minimum tread, no winders, a maximum height between landings of twelve feet (12'), minimum landing dimensions of forty-four inches (44"), landings at each exit door, and handrails on both sides. Exit(s) to fire escapes shall be at least thirty-six inches (36") wide, and the fire-escape door shall swing outward. All treads and risers shall be of the same height and width throughout the entire stairway, not including landings. II/III
(15) Facilities with three (3) or more floors shall comply with the provisions of Chapter 320, RSMo, which requires that outside stairways be constructed of iron or steel. II
(16) Door locks shall be of a type that can be opened from the inside by turning the knob or operating a simple device that will release the lock, or shall meet the requirements of Section 19.2 of NFPA 101, 2000 edition. Only one (1) lock will be permitted on any one (1) door. I/II
(17) All exit doors in existing licensed facilities shall be at least thirty inches (30") wide. II
(18) All exit doors in new facilities shall be at least forty-four inches (44") wide. II
(19) In all facilities, all exit doors and vestibule doors shall swing outward in the direction of exit travel. II
(20) In all existing licensed facilities, all horizontal exit doors in fire walls and all doors in smoke barrier partitions may swing in either direction. These doors normally may be open, but shall be automatically self-closing upon activation of the fire alarm system. They shall be capable of being manually released to self-closing action. II/III
(21) Facilities shall maintain corridors to be free of obstruction, equipment, or supplies not in use. Doors to resident rooms shall not swing into the corridor. II/III
(22) Facilities shall place signs bearing the word EXIT in plain, legible block letters at each required exit, except at doors directly from rooms to exit corridors or passageways. II
(23) Wherever necessary, the facility shall place additional signs in corridors and passageways to indicate the exit's direction. Letters on these signs shall be at least six inches (6") high and principle strokes three-fourths inch (3/4") wide, except that the letters of internally illuminated exit signs may be not less than four inches (4") high. III
(24) Facilities shall maintain all exit and directional signs to be clearly legible and electrically illuminated at all times by acceptable means such as emergency lighting when lighting fails. II
(25) Facilities shall have emergency lighting of sufficient intensity to provide for the safety of residents and other people using any exit, stairway, and corridor. The lighting shall be supplied by an emergency service, an automatic emergency generator or battery lighting system. This emergency lighting system shall be equipped with an automatic transfer switch. In an existing licensed facility, battery lights, if used, shall be wet cell units or other rechargeable-type batteries that shall be UL-approved and capable of operating the light for at least one and one-half (1 1/2) hours. Battery-operated emergency lighting shall be tested for at least thirty (30) seconds every thirty (30) days, and an annual function test shall be conducted for the full operational duration of one and one-half (1 1/2) hours. Records of these tests shall be documented and maintained for review. II
(26) If existing licensed facilities have laundry chutes, dumbwaiter shafts, or other similar vertical shafts, they shall have a fire resistance rating of at least one (1) hour if serving three (3) or fewer stories. Enclosures serving four (4) or more stories shall have at least a two- (2-) hour fire-rated enclosure. These chute or shaft doors shall be self-closing or shall have any other approved device that will guarantee separation between floors. II
(27) Existing licensed multistoried facilities shall provide a smoke separation barrier between the basement and the first floor and the floors of resident-use areas. At a minimum, this barrier shall consist of one-half inch (1/2") gypsum board, plaster, or equivalent. There shall be a one and three-fourths inch (1 3/4") thick solid-core wood door, or equivalent, at the top or bottom of the stairs. If the door is glazed, it shall be glazed with wired glass. II
(28) Each floor accessed by residents shall be divided into at least two (2) smoke sections with each section not exceeding one hundred fifty feet (150') in length or width. If the floor's dimensions do not exceed seventy-five feet (75') in length or width, a division of the the floor into two (2) smoke sections will not be required. II
(29) Each smoke section shall be separated by one- (1-) hour fire-rated walls that are continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty-(20-) minute fire rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the fire alarm system. II
(30) Existing licensed facilities shall have attached self-closing devices on all doors providing separation between floors. If the doors are to be held open, they shall have electromagnetic hold-open devices that are interconnected with either a smoke alarm or with other smoke-sensitive fire extinguishment or alarm systems in the building. II/III
(31) Smoking shall be permitted only in designated areas. Areas where smoking is permitted shall be directly supervised unless the resident has been assessed by the facility and determined capable of smoking unassisted. At least annually, the facility shall reassess those residents the facility has determined to be capable of smoking unsupervised and shall also reassess such resident when changes in his or her condition indicate the resident may no longer be capable of smoking without supervision. The facility shall document this assessment in the resident's medical record. II
(32) Designated smoking areas shall have ashtrays of noncombustible material and of safe design. The contents of ashtrays shall be disposed of properly in receptacles made of noncombustible material. II/III
(33) Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan to meet potential emergencies or disasters and shall request consultation and assistance annually from a local fire unit for review of fire and evacuation plans. If the consultation cannot be obtained, the facility shall inform the state fire marshal in writing and request assistance in review of the plan. An up-to-date copy of the facility's entire plan shall be provided to the local jurisdiction's emergency management director. II/III
(B) The plan shall include, but is not limited to-
1. A phased response ranging from relocation of residents to an immediate area within the facility; relocation to an area of refuge, if applicable; or to total building evacuation. This phased response part of the plan shall be consistent with the direction of the local fire unit or state fire marshal and shall be appropriate for the fire or emergency;
2. Written instructions for evacuation of each floor including evacuation to areas of refuge, if applicable, and floor plan showing the location of exits, fire alarm pull stations, fire extinguishers, and any areas of refuge;
3. Evacuating residents, if necessary, from an area of refuge to a point of safety outside the building;
4. The location of any additional water sources on the property such as cisterns, wells, lagoons, ponds, or creeks;
5. Procedures for the safety and comfort of residents evacuated;
6. Staffing assignments;
7. Instructions for staff to call the fire department or other outside emergency services;
8. Instructions for staff to call alternative resource(s) for housing residents, if necessary;
9. Administrative staff responsibilities; and
10. Designation of a staff member to be responsible for accounting for all residents' whereabouts. II/III
(C) The written plan shall be accessible at all times and an evacuation diagram shall be posted on each floor in a conspicuous place so that employees and residents can become familiar with the plan and routes to safety. II/III
(D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a simulated resident evacuation that involves the local fire department or emergency service at least once a year. II/III
(E) The fire alarm shall be activated during all fire drills unless the drill is conducted between 9 p.m. and 6 a.m., when a facility-generated predetermined message is acceptable in lieu of the audible and visual components of the fire alarm. II/III
(F) The facility shall keep a record of all fire drills including the simulated resident evacuation. The record shall include the time, date, personnel participating, length of time to complete the fire drill, and a narrative notation of any special problems. III
(34) Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill evaluations. II/III
(B) The training shall include, but is not limited to, the following:
1. Prevention of fire ignition, detection of fire, and control of fire development;
2. Confinement of the effects of fire;
3. Procedures for moving residents to an area of refuge, if applicable;
4. Use of alarms;
5. Transmission of alarms to the fire department;
6. Response to alarms;
7. Isolation of fire;
8. Evacuation of the immediate area and building;
9. Preparation of floors and facility for evacuation; and
10. Use of the evacuation plan required by section (33) of this rule. II/III
(35) The use of wood- or gas-burning fireplaces will be permitted only if the fireplaces are built of firebrick or metal, enclosed by masonry, and have metal or tempered glass screens. The chimneys shall be of masonry construction with flue linings that have at least eight inches (8") of masonry separating the flue lining and the fireplace from any combustible material. All fireplaces shall be installed, operated, and maintained in a safe manner. Fireplaces not in compliance with these requirements may be provided if they are for decorative purposes only or if they are equipped with decorative-type electric logs or other electric heaters which bear the UL label and are constructed of electrical components complying with and installed in compliance with the National Electrical Code, incorporated by reference in this rule. Fireplaces meeting standards set forth in NFPA 211, 2000 edition, are considered in compliance with this rule. II/III
(36) All electric or gas clothes dryers shall be vented to the outside and the lint trap cleaned regularly. II/III
(37) In existing licensed facilities, all wall and ceiling surfaces shall be smooth and free of highly-combustible materials. II/III
(38) All curtains in resident-use areas shall be rendered and maintained flame-resistant in accordance with NFPA 701, 1999 edition. II/III
(39) All new floor covering installed in buildings that do not have a sprinkler system shall be Class I in accordance with NFPA 253, 2000 edition. II/III
(40) Trash and Rubbish Disposal Requirements.
(A) Only metal or UL- or FM-approved wastebaskets shall be used for the collection of trash. II
(B) The facility shall maintain the exterior premises in a manner as to provide for fire safety. II
(C) Trash shall be removed from the premises as often as necessary to prevent fire hazards and public health nuisance. II
(D) No trash shall be burned within fifty feet (50') of any facility except in an approved incinerator I/II
(E) Trash may be burned only in a masonry or metal container The container shall be equipped with a metal cover with openings no larger than one-half inch (1/2") in size. II/III
(41) Minimum Staffing for Safety and Protective Oversight to Residents.
(A) In a building that is of fire-resistant construction or a building with a sprinkler system, minimum staffing shall be the following:

TimePersonnelResidents
7 a.m. to 3 p.m. (Day) 1 3-10*
3 p.m. to 11 p.m. (Evening) 1 3-15*
11 p.m. to 7 a.m. (Night) 1 3-20*

*One (1) additional staff person for every fraction after that. I/II

(B) In a building that is of nonfire-resistant construction or a building that has a sprinkler system exemption, minimum staffing shall be the following:

TimePersonnelResidents
7 a.m. to 3 p.m. (Day) 1 3-10*
3 p.m. to 11 p.m. (Evening) 1 3-15*
11 p.m. to 7 a.m. (Night) 1 3-15*

*One (1) additional staff person for every fraction after that. I/II

19 CSR 30-85.022

AUTHORITY: sections 198.074 and 198.079, RSMo Supp. 2011.* This rule originally filed as 13 CSR 15-14.022. Original rule filed July 13, 1983, effective Oct. 13, 1983. Amended: Filed Sept. 12, 1984, effective Dec. 13, 1984. Amended: Filed Aug. 1, 1988, effective Nov. 11 , 1988. Amended: Filed May 11 , 1998, effective Dec. 30, 1998. Emergency amendment filed May 12, 1999, effective May 22, 1999, expired Feb. 24, 2000. Amended: Filed July 13, 1999, effective Jan. 30, 2000. Moved to 19 CSR 30-85.022, effective Aug. 28, 2001. Emergency amendment filed Nov. 24, 2008, effective Dec. 4, 2008, expired June 1, 2009. Amended: Filed Nov. 24, 2008, effective May 30, 2009. Amended: Filed March 15, 2012, effective Oct. 30, 2012.

*Original authority: 198.074, RSMo 2007 and 198.079, RSMo 1979, amended 2007.